Bill Text: IL HB0051 | 2021-2022 | 102nd General Assembly | Engrossed
NOTE: There are more recent revisions of this legislation. Read Latest Draft
Bill Title: Amends the Smoke Detector Act. Removes language providing that specified smoke detector requirements shall not apply to dwelling units and hotels within municipalities with a population over 1,000,000 inhabitants.
Sponsorship: Slight Partisan Bill (Democrat 2-1)
Status: (Passed) 2021-07-09 - Public Act . . . . . . . . . 102-0046 [HB0051 Detail]
Download: Illinois-2021-HB0051-Engrossed.html
Bill Title: Amends the Smoke Detector Act. Removes language providing that specified smoke detector requirements shall not apply to dwelling units and hotels within municipalities with a population over 1,000,000 inhabitants.
Sponsorship: Slight Partisan Bill (Democrat 2-1)
Status: (Passed) 2021-07-09 - Public Act . . . . . . . . . 102-0046 [HB0051 Detail]
Download: Illinois-2021-HB0051-Engrossed.html
| |||||||
| |||||||
| |||||||
| 1 | AN ACT concerning safety.
| ||||||
| 2 | Be it enacted by the People of the State of Illinois,
| ||||||
| 3 | represented in the General Assembly:
| ||||||
| 4 | Section 5. The Smoke Detector Act is amended by changing | ||||||
| 5 | Section 3 as follows:
| ||||||
| 6 | (425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
| ||||||
| 7 | (Text of Section before amendment by P.A. 100-200)
| ||||||
| 8 | Sec. 3.
(a) Every dwelling unit or hotel shall be equipped | ||||||
| 9 | with at least one
approved smoke detector in an operating | ||||||
| 10 | condition within 15 feet of every room
used for sleeping | ||||||
| 11 | purposes. The detector shall be installed on the ceiling
and | ||||||
| 12 | at least 6 inches from any wall, or on a wall located between 4 | ||||||
| 13 | and 6
inches from the ceiling.
| ||||||
| 14 | (b) Every single family residence shall have at least one | ||||||
| 15 | approved smoke
detector installed on every story of the | ||||||
| 16 | dwelling unit, including basements
but not including | ||||||
| 17 | unoccupied attics. In dwelling units with split levels,
a | ||||||
| 18 | smoke detector installed on the upper level shall suffice for | ||||||
| 19 | the
adjacent lower level if the lower level is less than one | ||||||
| 20 | full story below
the upper level; however, if there is an | ||||||
| 21 | intervening door between the
adjacent levels, a smoke detector | ||||||
| 22 | shall be installed on each level.
| ||||||
| 23 | (c) Every structure which (1) contains more than one | ||||||
| |||||||
| |||||||
| 1 | dwelling unit, or
(2) contains at least one dwelling unit and | ||||||
| 2 | is a mixed-use structure, shall
contain at least one approved | ||||||
| 3 | smoke detector at the uppermost ceiling of
each interior | ||||||
| 4 | stairwell. The detector shall be installed on the ceiling,
at | ||||||
| 5 | least 6 inches from the wall, or on a wall located between 4 | ||||||
| 6 | and 6
inches from the ceiling.
| ||||||
| 7 | (d) It shall be the responsibility of the owner of a | ||||||
| 8 | structure to supply
and install all required detectors. The | ||||||
| 9 | owner shall be responsible for
making reasonable efforts to | ||||||
| 10 | test and maintain detectors in common
stairwells and hallways. | ||||||
| 11 | It shall be the responsibility of a tenant to
test and to | ||||||
| 12 | provide general maintenance for the detectors within the
| ||||||
| 13 | tenant's dwelling unit or rooming unit, and to notify the | ||||||
| 14 | owner or the
authorized agent of the owner in writing of any | ||||||
| 15 | deficiencies which the
tenant cannot correct. The owner shall | ||||||
| 16 | be responsible for providing one
tenant per dwelling unit with | ||||||
| 17 | written information regarding detector
testing and | ||||||
| 18 | maintenance.
| ||||||
| 19 | The tenant shall be responsible for replacement of any | ||||||
| 20 | required batteries
in the smoke detectors in the tenant's | ||||||
| 21 | dwelling unit, except that the owner
shall ensure that such | ||||||
| 22 | batteries are in operating condition at the time
the tenant | ||||||
| 23 | takes possession of the dwelling unit. The tenant shall | ||||||
| 24 | provide
the owner or the authorized agent of the owner with | ||||||
| 25 | access to the dwelling
unit to correct any deficiencies in the | ||||||
| 26 | smoke detector which have been
reported in writing to the | ||||||
| |||||||
| |||||||
| 1 | owner or the authorized agent of the owner.
| ||||||
| 2 | (e) The requirements of this Section shall apply to any | ||||||
| 3 | dwelling unit
in existence on July 1, 1988, beginning on that | ||||||
| 4 | date. Except as provided
in subsections (f) and (g), the smoke | ||||||
| 5 | detectors required in such dwelling
units may be either | ||||||
| 6 | battery powered or wired into the structure's AC power
line, | ||||||
| 7 | and need not be interconnected.
| ||||||
| 8 | (f) In the case of any dwelling unit that is newly | ||||||
| 9 | constructed,
reconstructed, or substantially remodelled after | ||||||
| 10 | December 31, 1987, the
requirements of this Section shall | ||||||
| 11 | apply beginning on the first day of
occupancy of the dwelling | ||||||
| 12 | unit after such construction, reconstruction or
substantial | ||||||
| 13 | remodelling. The smoke detectors required in such dwelling
| ||||||
| 14 | unit shall be permanently wired into the structure's AC power | ||||||
| 15 | line, and if
more than one detector is required to be installed | ||||||
| 16 | within the dwelling
unit, the detectors shall be wired so that | ||||||
| 17 | the actuation of one detector
will actuate all the detectors | ||||||
| 18 | in the dwelling unit.
| ||||||
| 19 | In the case of any dwelling unit that is newly | ||||||
| 20 | constructed,
reconstructed, or substantially remodeled on or | ||||||
| 21 | after January 1, 2011, smoke detectors permanently wired into | ||||||
| 22 | the structure's AC power line must also maintain an | ||||||
| 23 | alternative back-up power source, which may be either a | ||||||
| 24 | battery or batteries or an emergency generator. | ||||||
| 25 | (g) Every hotel shall be equipped with operational | ||||||
| 26 | portable
smoke-detecting alarm devices for the deaf and | ||||||
| |||||||
| |||||||
| 1 | hearing impaired of audible
and visual design, available for | ||||||
| 2 | units of occupancy.
| ||||||
| 3 | Specialized smoke detectors smoke-detectors for the deaf | ||||||
| 4 | and hearing impaired shall be
available upon request by guests | ||||||
| 5 | in such hotels at a rate
of at least one such smoke detector | ||||||
| 6 | per 75 occupancy units or portions
thereof, not to exceed 5 | ||||||
| 7 | such smoke detectors per hotel.
Incorporation or connection | ||||||
| 8 | into an existing interior alarm system, so as
to be capable of | ||||||
| 9 | being activated by the system, may be utilized in lieu of
the | ||||||
| 10 | portable alarms.
| ||||||
| 11 | Operators of any hotel shall post conspicuously at the | ||||||
| 12 | main desk a
permanent notice, in letters at least 3 inches in | ||||||
| 13 | height, stating that
smoke detector alarm devices for the deaf | ||||||
| 14 | and hearing impaired are
available. The proprietor may require | ||||||
| 15 | a refundable deposit for a portable
smoke detector not to | ||||||
| 16 | exceed the cost of the detector.
| ||||||
| 17 | (g-5) A hotel, as defined in this Act, shall be | ||||||
| 18 | responsible for installing and maintaining smoke detecting | ||||||
| 19 | equipment. | ||||||
| 20 | (h) Compliance with an applicable federal, State, or local | ||||||
| 21 | law or
building code which requires the installation and | ||||||
| 22 | maintenance of smoke
detectors in a manner different from this | ||||||
| 23 | Section, but providing a level of
safety for occupants which | ||||||
| 24 | is equal to or greater than that provided by
this Section, | ||||||
| 25 | shall be deemed to be in compliance with this Section, and
the | ||||||
| 26 | requirements of such more stringent law shall govern over the
| ||||||
| |||||||
| |||||||
| 1 | requirements of this Section.
| ||||||
| 2 | (Source: P.A. 96-1292, eff. 1-1-11; 97-447, eff. 1-1-12; | ||||||
| 3 | revised 8-19-20.)
| ||||||
| 4 | (Text of Section after amendment by P.A. 100-200)
| ||||||
| 5 | Sec. 3.
(a) Every dwelling unit or hotel shall be equipped | ||||||
| 6 | with at least one
approved smoke detector in an operating | ||||||
| 7 | condition within 15 feet of every room
used for sleeping | ||||||
| 8 | purposes. The detector shall be installed on the ceiling
and | ||||||
| 9 | at least 6 inches from any wall, or on a wall located between 4 | ||||||
| 10 | and 6
inches from the ceiling.
| ||||||
| 11 | (b) Every single family residence shall have at least one | ||||||
| 12 | approved smoke
detector installed on every story of the | ||||||
| 13 | dwelling unit, including basements
but not including | ||||||
| 14 | unoccupied attics. In dwelling units with split levels,
a | ||||||
| 15 | smoke detector installed on the upper level shall suffice for | ||||||
| 16 | the
adjacent lower level if the lower level is less than one | ||||||
| 17 | full story below
the upper level; however, if there is an | ||||||
| 18 | intervening door between the
adjacent levels, a smoke detector | ||||||
| 19 | shall be installed on each level.
| ||||||
| 20 | (c) Every structure which (1) contains more than one | ||||||
| 21 | dwelling unit, or
(2) contains at least one dwelling unit and | ||||||
| 22 | is a mixed-use structure, shall
contain at least one approved | ||||||
| 23 | smoke detector at the uppermost ceiling of
each interior | ||||||
| 24 | stairwell. The detector shall be installed on the ceiling,
at | ||||||
| 25 | least 6 inches from the wall, or on a wall located between 4 | ||||||
| |||||||
| |||||||
| 1 | and 6
inches from the ceiling.
| ||||||
| 2 | (d) It shall be the responsibility of the owner of a | ||||||
| 3 | structure to supply
and install all required detectors. The | ||||||
| 4 | owner shall be responsible for
making reasonable efforts to | ||||||
| 5 | test and maintain detectors in common
stairwells and hallways. | ||||||
| 6 | It shall be the responsibility of a tenant to
test and to | ||||||
| 7 | provide general maintenance for the detectors within the
| ||||||
| 8 | tenant's dwelling unit or rooming unit, and to notify the | ||||||
| 9 | owner or the
authorized agent of the owner in writing of any | ||||||
| 10 | deficiencies which the
tenant cannot correct. The owner shall | ||||||
| 11 | be responsible for providing one
tenant per dwelling unit with | ||||||
| 12 | written information regarding detector
testing and | ||||||
| 13 | maintenance.
| ||||||
| 14 | The tenant shall be responsible for replacement of any | ||||||
| 15 | required batteries
in the smoke detectors in the tenant's | ||||||
| 16 | dwelling unit, except that the owner
shall ensure that such | ||||||
| 17 | batteries are in operating condition at the time
the tenant | ||||||
| 18 | takes possession of the dwelling unit. The tenant shall | ||||||
| 19 | provide
the owner or the authorized agent of the owner with | ||||||
| 20 | access to the dwelling
unit to correct any deficiencies in the | ||||||
| 21 | smoke detector which have been
reported in writing to the | ||||||
| 22 | owner or the authorized agent of the owner.
| ||||||
| 23 | (e) The requirements of this Section shall apply to any | ||||||
| 24 | dwelling unit
in existence on July 1, 1988, beginning on that | ||||||
| 25 | date. Except as provided
in subsections (f) and (g), the smoke | ||||||
| 26 | detectors required in such dwelling
units may be either: | ||||||
| |||||||
| |||||||
| 1 | battery powered provided the battery is a self-contained, | ||||||
| 2 | non-removable, long-term long term battery, or wired into the | ||||||
| 3 | structure's AC power
line, and need not be interconnected.
| ||||||
| 4 | (1) The battery requirements of this Section shall | ||||||
| 5 | apply to battery-powered battery powered smoke detectors | ||||||
| 6 | that: (A) are in existence and exceed 10 years from the | ||||||
| 7 | date of their being manufactured; (B) fail fails to | ||||||
| 8 | respond to operability tests or otherwise malfunction | ||||||
| 9 | malfunctions; or (C) are newly installed. | ||||||
| 10 | (2) The battery requirements of this Section do not | ||||||
| 11 | apply to: (A) a fire alarm, smoke detector, smoke alarm, | ||||||
| 12 | or ancillary component that is electronically connected as | ||||||
| 13 | a part of a centrally monitored or supervised alarm | ||||||
| 14 | system; (B) a fire alarm, smoke detector, smoke alarm, or | ||||||
| 15 | ancillary component that uses: (i) a low-power radio | ||||||
| 16 | frequency wireless communication signal, or (ii) Wi-Fi or | ||||||
| 17 | other wireless Local Area Networking capability to send | ||||||
| 18 | and receive notifications to and from the Internet, such | ||||||
| 19 | as early low battery warnings before the device reaches a | ||||||
| 20 | critical low power level; or (C) such other devices as the | ||||||
| 21 | State Fire Marshal shall designate through its regulatory | ||||||
| 22 | process. | ||||||
| 23 | (f) In the case of any dwelling unit that is newly | ||||||
| 24 | constructed,
reconstructed, or substantially remodelled after | ||||||
| 25 | December 31, 1987, the
requirements of this Section shall | ||||||
| 26 | apply beginning on the first day of
occupancy of the dwelling | ||||||
| |||||||
| |||||||
| 1 | unit after such construction, reconstruction or
substantial | ||||||
| 2 | remodelling. The smoke detectors required in such dwelling
| ||||||
| 3 | unit shall be permanently wired into the structure's AC power | ||||||
| 4 | line, and if
more than one detector is required to be installed | ||||||
| 5 | within the dwelling
unit, the detectors shall be wired so that | ||||||
| 6 | the actuation of one detector
will actuate all the detectors | ||||||
| 7 | in the dwelling unit.
| ||||||
| 8 | In the case of any dwelling unit that is newly | ||||||
| 9 | constructed,
reconstructed, or substantially remodeled on or | ||||||
| 10 | after January 1, 2011, smoke detectors permanently wired into | ||||||
| 11 | the structure's AC power line must also maintain an | ||||||
| 12 | alternative back-up power source, which may be either a | ||||||
| 13 | battery or batteries or an emergency generator. | ||||||
| 14 | (g) Every hotel shall be equipped with operational | ||||||
| 15 | portable
smoke-detecting alarm devices for the deaf and | ||||||
| 16 | hearing impaired of audible
and visual design, available for | ||||||
| 17 | units of occupancy.
| ||||||
| 18 | Specialized smoke detectors smoke-detectors for the deaf | ||||||
| 19 | and hearing impaired shall be
available upon request by guests | ||||||
| 20 | in such hotels at a rate
of at least one such smoke detector | ||||||
| 21 | per 75 occupancy units or portions
thereof, not to exceed 5 | ||||||
| 22 | such smoke detectors per hotel.
Incorporation or connection | ||||||
| 23 | into an existing interior alarm system, so as
to be capable of | ||||||
| 24 | being activated by the system, may be utilized in lieu of
the | ||||||
| 25 | portable alarms.
| ||||||
| 26 | Operators of any hotel shall post conspicuously at the | ||||||
| |||||||
| |||||||
| 1 | main desk a
permanent notice, in letters at least 3 inches in | ||||||
| 2 | height, stating that
smoke detector alarm devices for the deaf | ||||||
| 3 | and hearing impaired are
available. The proprietor may require | ||||||
| 4 | a refundable deposit for a portable
smoke detector not to | ||||||
| 5 | exceed the cost of the detector.
| ||||||
| 6 | (g-5) A hotel, as defined in this Act, shall be | ||||||
| 7 | responsible for installing and maintaining smoke detecting | ||||||
| 8 | equipment. | ||||||
| 9 | (h) Compliance with an applicable federal, State, or local | ||||||
| 10 | law or
building code which requires the installation and | ||||||
| 11 | maintenance of smoke
detectors in a manner different from this | ||||||
| 12 | Section, but providing a level of
safety for occupants which | ||||||
| 13 | is equal to or greater than that provided by
this Section, | ||||||
| 14 | shall be deemed to be in compliance with this Section, and
the | ||||||
| 15 | requirements of such more stringent law shall govern over the
| ||||||
| 16 | requirements of this Section.
| ||||||
| 17 | (i) (Blank). The requirements of this Section shall not | ||||||
| 18 | apply to dwelling units and hotels within municipalities with | ||||||
| 19 | a population over 1,000,000 inhabitants. | ||||||
| 20 | (Source: P.A. 100-200, eff. 1-1-23; revised 8-19-20.)
| ||||||
| 21 | Section 95. No acceleration or delay. Where this Act makes | ||||||
| 22 | changes in a statute that is represented in this Act by text | ||||||
| 23 | that is not yet or no longer in effect (for example, a Section | ||||||
| 24 | represented by multiple versions), the use of that text does | ||||||
| 25 | not accelerate or delay the taking effect of (i) the changes | ||||||
| |||||||
| |||||||
| 1 | made by this Act or (ii) provisions derived from any other | ||||||
| 2 | Public Act.
| ||||||